1-1/2" FIRE HOSE
TO EDUCTOR
1-1/2" FIRE HOSE
1-1/2" FIRE HOSE
WYE-GATE
VARI-NOZZLE
2-1/2" FIRE
HOSE JUMPER
GREATER THAN
20 FEET, BUT NOT
3" HARD RUBBER
MORE THAN 39 FEET
SUCTION HOSE
3" MALE X 2-1/2"
FEMALE REDUCER
2-1/2" EDUCTOR
(DISCHARGE SIZE)
DCf0530
Figure 5-30. Fire-fighting hookup.
WARNING
An air-cooled single-cylinder, four-cycle diesel
The diesel engine exhaust contains
engine rated at 10 horsepower powers the P-100 pump.
poisonous carbon monoxide. Never use the
A mechanical governor is used to control the speed of
pump unit in poorly ventilated locations, such as
the engine. It contains a 1.45 gallon fuel tank that will
enclosed spaces. If such operation is
unavoidable, provide proper ventilation and use
an approved exhaust hose routed to the weather
decks.
hose. (See warning.)
Figure 5-31. Fire-fighting hookp for suction lifts greater than 20 feet.
5-17