Figure 5-29. P-100 portable diesel engine-driven centrifugal pump.
Figure 5-32. A typical P-100 dewatering configuration.

Damage Controlman
Page Navigation
  82    83    84    85    86  87  88    89    90    91    92  
img
1-1/2" FIRE HOSE
TO EDUCTOR
1-1/2" FIRE HOSE
1-1/2" FIRE HOSE
WYE-GATE
VARI-NOZZLE
2-1/2" FIRE
HOSE JUMPER
GREATER THAN
20 FEET, BUT NOT
3" HARD RUBBER
MORE THAN 39 FEET
SUCTION HOSE
3" MALE X 2-1/2"
FEMALE REDUCER
2-1/2" EDUCTOR
(DISCHARGE SIZE)
DCf0530
Figure 5-30. Fire-fighting hookup.
WARNING
An air-cooled single-cylinder, four-cycle diesel
The diesel engine exhaust contains
engine rated at 10 horsepower powers the P-100 pump.
poisonous carbon monoxide. Never use the
A mechanical governor is used to control the speed of
pump unit in poorly ventilated locations, such as
the engine. It contains a 1.45 gallon fuel tank that will
enclosed spaces. If such operation is
allow up to 2.75 hours of operation. The engine
unavoidable, provide proper ventilation and use
exhaust muffler is constructed to receive an exhaust
an approved exhaust hose routed to the weather
decks.
hose. (See warning.)
Figure 5-31. Fire-fighting hookp for suction lifts greater than 20 feet.
5-17